20.3 Auto Power Save Time Read
This command is used in order to read the setting of Auto Power Save Time.
1) The controller requests the monitor to reply Time setting.
Header Message Check code Delimiter
SOH-'0'-Monitor ID-
'0'-'A'-'0'-'8'
STX-'C'-'A'-'0'-'B'-'0'-'2'-ETX BCC CR
Header
SOH (01h): Start of Header
'0' (30h): Reserved
Monitor ID: Specify the Monitor ID of which you want to change a setting.
Ex.) If Monitor ID is '1', specify 'A'.
'0' (30h): Message sender is the controller.
'A' (41h): Message type is "Command".
'0'-'8'(30h,38h): Message length (8byte)
Message
STX (02h): Start of Message
'C'-'A'-'0'-'B' (43h, 41h, 30h, 42h): Power Save Mode command
'0'-'2' (30h, 30h): Auto Power Save Read
ETX (03h): End of Message
Check code
BCC: Block Check Code
Refer to the section 4.3 “Check code” for a BCC calculation.
Delimiter
CR (0Dh): End of packet
2) The monitor replies Time to the controller.
Header Message Check code
Delimiter
SOH-'0'-'0'-Monitor ID-
'B'-'0'-'A'
STX-'C'-'B'-'0'-'B'-'0'-'2'-TIME-ETX BCC CR
Header
SOH (01h): Start of Header
'0' (30h): Reserved
'0' (30h): Message receiver is the controller.
Monitor ID: Indicate a replying Monitor ID.
Ex.) When this byte is set to ‘A’, replying monitor’s ID is ‘1’.
'B' (42h): Message type is "Command reply".
'0'-'A'(30h,41h): Message length (10byte)
Message
STX (02h): Start of Message
'C'-'B'-'0'-'B' (43h, 42h, 30h, 42h): Power Save Mode Reply
'0'-'2' (30h, 32h): Auto Power Save Time Read
TIME: AUTO POWER SAVE TIME (sec.)
00h (30h, 30h) – 78h (37h, 38h): 1 (5dec.) – 120 (600sec.)
ETX (03h): End of Message
Check code
BCC: Block Check Code
Refer to the section 4.3 “Check code” for a BCC calculation.
Delimiter
CR (0Dh): End of packet